You should then address the specific scope of your work in your energy analysis. On the PW1 form in Section 10, you need to check compliance. Any new building that is required to comply with the residential provisions of the 2016 NYCECC is required to perform both IA6 Air sealing & insulation – visual and IA7 Air sealing and insulation - testing and indicate "yes" in Section 3A of the TR8 form.Īny new building that is required to comply with the commercial provisions of 2016 NYCECC and is between 25,000 and 50,000 sqft of floor area and less than or equal to 75 feet in height is required to perform IIA7 Air sealing and insulation - testing and indicate "yes" in Section 3A of the TR8 form.Īny new building that is required to comply with the commercial provisions of 2016 NYCECC and is greater than or equal to 50,000 sqft in floor area is required to perform both IIA6 Air sealing & insulation – visual, if the Air Barrier Continuity Plan is the chosen method of compliance, or IIA7 Air sealing and insulation – testing, if whole building pressurization testing is the chosen method of compliance.Īll other buildings required to comply with the commercial provisions of the 2016 NYCECC shall require either IIA6 Air sealing & insulation – visual or IIA7 Air sealing and insulation - testing.